Modeling and dynamics study of large scale PV system connected Malaysian grid under different fault conditions

Al-Shetwi, Ali Q. and Muhamad Zahim, Sujod (2017) Modeling and dynamics study of large scale PV system connected Malaysian grid under different fault conditions. In: International Conference on Advances in Electrical, Electronic and Systems Engineering (ICAEES 2016) , 14-16 November 2016 , Putrajaya Marriott Hotel, Putrajaya; Malaysia. pp. 488-494.. ISBN 978-1-5090-2889-4

[img] Pdf
Modeling and Dynamics Study of Large Scale PV System Connected Malaysian Grid under Different Fault Conditions.pdf
Restricted to Repository staff only

Download (1MB) | Request a copy
[img]
Preview
Pdf
Modeling and Dynamics Study of Large Scale PV System Connected Malaysian Grid under Different Fault Conditions 1.pdf

Download (115kB) | Preview

Abstract

The installation of photovoltaic power plants and integration with electric grid has become more widespread. As there is a significant increase in the size and capacity of grid-connected power plants, the stability and reliability of the grid become more important. A 1.5 MW PV station connected to the distribution side of the Malaysian grid via a voltage source inverter is modeled and simulated using Matlab/Simulink. This study presents the modeling of PV module behavior and characteristics based on the mathematical model equivalent circuit. The Simulink was run to simulate PV array sizing depending on perturb and observed maximum power point technique to enhance the efficiency of modules, and obtain maximum available power using variable perturbation step size dependent on power changes. The simulation result was matched to the results of sizing calculation. The inverter control system modeling and park transformation were carried out. Phase locked loop was used to track the grid frequency and voltage. The Malaysian grid-connected PV system is designed and modeled according to the regulations and guidelines of Tenaga Nasional Berhad concerning grid-integration of PV power generation system to LV and MV networks. Finally, this paper analyzes the dynamic response of the proposed PV plant under various types of symmetrical and non-symmetrical grid faults. The results indicated that the short circuit faults in the distribution grid side had disturbing effects on the optimal operation performance of PV systems. Whereas, the influence of grid faults depends on the fault type. In addition to that, the simulation result proved that the symmetrical fault has higher impact on PV system operation than non-symmetrical faults.

Item Type: Conference or Workshop Item (Speech)
Additional Information: Indexed by Scopus
Uncontrolled Keywords: Fault analysis; PV system modeling; Gridconnected inverter; Malaysian grid; Distribution system.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Faculty/Division: Faculty of Electrical & Electronic Engineering
Institute of Postgraduate Studies
Depositing User: Mrs. Neng Sury Sulaiman
Date Deposited: 18 Jul 2018 08:22
Last Modified: 18 Oct 2019 02:40
URI: http://umpir.ump.edu.my/id/eprint/18233
Download Statistic: View Download Statistics

Actions (login required)

View Item View Item